Backflow Testing for Austin by HHCC
Servicing the entire Metro Area including Cedar Park, Georgetown, and Round Rock
Methods and Devices
for the Prevention of
Backflow and
Back-Siphonage
A wide choice of devices
exists that can be used to
prevent backsiphonage and
backpressure from adding
contaminated fluids or gases
into a potable water supply
system. Generally, the selection
of the proper device to use is
based upon the degree of hazard
posed by the cross-connection.
Additional considerations are
based upon piping size, location,
and the potential need to
periodically test the devices to
insure proper operation.
There are six basic types of
devices that can be used to
correct cross-connections: air
gaps, barometric loops, vacuum
breakers—both atmospheric
and pressure type, double check
with intermediate atmospheric
vent, double check valve
assemblies, and reduced pressure
principle devices. In general, all
manufacturers of these devices,
with the exception of the
barometric loop, produce them
to one or more of three basic
standards, thus insuring the
public that dependable devices
are being utilized and marketed.
The major standards in the
industry are: American Society
of Sanitary Engineers ASSE),
American Water Works Association
(AWWA), and the University
of California Foundation for
Cross-Connection Control and
Hydraulic Research.
Air Gap
Air gaps are non-mechanical
backflow preventers that are
very effective devices to be used
where either backsiphonage or
backpressure conditions may
exist. Their use is as old as
piping and plumbing itself, but only relatively recently have
standards been issued that
standardize their design. In
general, the air gap must be
twice the supply pipe diameter
but never less than one inch.
An air gap, although an
extremely effective backflow
preventer when used to prevent
backsiphonage and backpressure
conditions, does interrupt
the piping flow with corresponding
loss of pressure for
subsequent use. Consequently,
air gaps are primarily used at
end of the line service where reservoirs or storage tanks are
desired. When contemplating
the use of an air gap, some
other considerations are:
(1) In a continuous piping
system, each air gap requires
the added expense of reservoirs
and secondary pumping
systems. (2) The air gap may be easily
defeated in the event that the
“2D” requirement was purposely
or inadvertently compromised.
Excessive splash may be encountered
in the event that higher
than anticipated pressures or
flows occur. The splash may be a
cosmetic or true potential
hazard—the simple solution
being to reduce the “2D”
dimension by thrusting the
supply pipe into the receiving
funnel. By so doing, the air gap
is defeated.
(3) At an air gap, we expose the
water to the surrounding air
with its inherent bacteria, dust
particles, and other airborne
pollutants or contaminants. In
addition, the aspiration effect of
the flowing water can drag down
surrounding pollutants into the
reservoir or holding tank.
(4) Free chlorine can come out of
treated water as a result of the air
gap and the resulting splash and
churning effect as the water
enters the holding tanks. This
reduces the ability of the water
to withstand bacteria contamination
during long term storage.
(5) For the above reasons, air
gaps must be inspected as
frequently as mechanical
backflow preventers. They are
not exempt from an in-depth
cross connection control program
requiring periodic inspection
of all backflow devices.
Air gaps may be fabricated
from commercially available
plumbing components or
purchased as separate units and
integrated into plumbing and
piping systems.
Barometric Loop
The barometric loop consists of
a continuous section of supply
piping that abruptly rises to a
height of approximately 35 feet
and then returns back down to
the originating level. It is a loop
in the piping system that
effectively protects against
backsiphonage. It may not be
used to protect against backpressure.
Its operation, in the
protection against backsiphonage,
is based upon the
principle that a water column,
at sea level pressure, will not
rise above 33.9 feet.
In general, barometric
loops are locally fabricated, and
are 35 feet high.
Atmospheric Vacuum Breaker
These devices are among the
simplest and least expensive
mechanical types of backflow
preventers and, when installed
properly, can provide excellent
protection against backsiphonage.
They must not be
utilized to protect against
backpressure conditions.
Construction consists usually of a polyethylene float which is
free to travel on a shaft and seal
in the uppermost position
against atmosphere with an
elastomeric disc. Water flow
lifts the float, which then causes
the disc to seal. Water pressure
keeps the float in the upward
sealed position.
Termination of
the water supply will cause the
disc to drop down venting the
unit to atmosphere and thereby
opening downstream piping to
atmospheric pressure, thus
preventing backsiphonage.
Figure 15 shows a typical
atmospheric breaker.
In general, these devices
are available in ½-inch through
3-inch size and must be
installed vertically, must not
have shutoffs downstream, and must be installed at least
6-inches higher than the final
outlet. They cannot be tested
once they are installed in the
plumbing system, but are, for
the most part, dependable,
trouble-free devices for
backsiphonage protection.
Hose Bibb
Vacuum Breakers
These small devices are a
specialized application of the
atmospheric vacuum breaker.
They are generally attached to
sill cocks and in turn are connected to hose supplied
outlets such as garden hoses,
slop sink hoses, spray outlets,
etc. They consist of a spring
loaded check valve that seals
against an atmospheric outlet
when water supply pressure is
turned on. When the water supply is
turned off, the device vents to
atmosphere, thus protecting
against backsiphonage conditions.
They should not be used
as backpressure devices. Manual
drain options are available,
together with tamper-proof
versions.
Pressure Vacuum Breakers
This device is an outgrowth of
the atmospheric vacuum
breaker and evolved in response
to a need to have an atmospheric
vacuum breaker that could be
utilized under constant pressure
and that could be tested in line.
A spring on top of the disc and
float assembly, two added gate
valves, test cocks, and an
additional first check, provided
the answer to achieve this
device.
These units are available in
the general configurations in sizes
½-inch through 10-inch and
have broad usage in the
agriculture and irrigation
market.
Again, these devices may
be used under constant pressure
but do not protect against
backpressure conditions. As a
result, installation must be at
least 6- to 12-inches higher than the existing outlet. A spill resistant pressure
vacuum breaker (SVB) is
available that is a modification
to the standard pressure
vacuum breaker but specifically
designed to minimize water
spillage. Installation and
hydraulic requirements are
similar to the standard pressure
vacuum breaker and the
devices are recommended for
internal use.
Double Check with
Intermediate
Atmospheric Vent
The need to provide a compact
device in ½-inch and ¾-inch
pipe sizes that protects against
moderate hazards, is capable of
being used under constant
pressure and that protects
against backpressure, resulted
in this unique backflow
preventer. Construction is
basically a double check valve
having an atmospheric vent
located between the two checks.
Line pressure keeps the
vent closed, but zero supply
pressure or backsiphonage will
open the inner chamber to
atmosphere. With this device,
extra protection is obtained
through the atmospheric vent
capability. Figure 23 shows a
typical use of the device on a
residential boiler supply line.
Double Check Valve
A double check valve is
essentially two single check
valves coupled within one body
and furnished with test cocks
and two tightly closing gate
valves.
The test capability feature
gives this device a big advantage
over the use of two
independent check valves in
that it can be readily tested to
determine if either or both
check valves are inoperative
or fouled by debris. Each check
is spring loaded closed and
requires approximately a pound
of pressure to open.
This spring loading
provides the ability to “bite”
through small debris and still
seal—a protection feature not
prevalent in unloaded swing
check valves.
Double checks are commonly
used to protect against low to
medium hazard installations
such as food processing steam
kettles and apartment projects.
They may be used under
continuous pressure and protect
against both backsiphonage and
backpressure conditions.
Double Check Detector
Check
This device is an outgrowth of
the double check valve and is
primarily utilized in fire line
installations. Its purpose is to
protect the potable supply line
from possible contamination or
pollution from fire line chemical
additives, booster pump fire
line backpressure, stagnant
“black water” that sits in fire
lines over extended periods of
time, the addition of “raw”
water through outside fire
pumper connections (Siamese
outlets), and the detection of
any water movement in the fire
line water due to fire line
leakage or deliberate water
theft. It consists of two, spring
loaded check valves, a bypass
assembly with water meter and
double check valve, and two
tightly closing gate valves. The addition of test
cocks makes the device testable
to insure proper operation of
both the primary checks and the bypass check valve. In the
event of very low fire line water
usage, (theft of water) the low
pressure drop inherent in the
bypass system permits the low
flow of water to be metered
through the bypass system. In a
high flow demand, associated
with deluge fire capability, the
main check valves open,
permitting high volume, low
restricted flow, through the two
large spring loaded check
valves
Residential Dual Check
The need to furnish reliable and
inexpensive backsiphonage and
backpressure protection for
individual residences resulted in
the debut of the residential dual
check. Protection of the main
potable supply from household
hazards such as home photograph
chemicals, toxic insect
and garden sprays, termite
control pesticides used by
exterminators, etc., reinforced,
a true need for such a device.
It is sized for ½-, ¾-, and
1-inch service lines and is
installed immediately downstream
of the water meter. The
use of plastic check modules
and elimination of test cocks
and gate valves keeps the cost
reasonable while providing
good, dependable protection.
Reduced Pressure
Principle Backflow
Preventer
Maximum protection is
achieved against backsiphonage
and back- pressure conditions
utilizing reduced pressure
principle backflow preventers.
These devices are essentially
modified double check valves
with an atmospheric vent
capability placed between the
two checks and designed such
that this “zone” between the
two checks is always kept at
least two pounds less than the
supply pressure. With this
design criteria, the reduced
pressure principle backflow
preventer can provide protection
against backsiphonage and
backpressure when both the
first and second checks become
fouled. They can be used under
constant pressure and at high
hazard installations. They are
furnished with test cocks and
gate valves to enable testing
and are available in sizes ¾-inch
through 10 inch.

HHCC is available for all your backflow needs. To request more information, schedule an appointment or request service: PLEASE CLICK HERE.
|